Key takeaways
  • Usable energy at 80% DOD: 1.0 / 3.2 / 2.0 / 4.1 kWh for 12V 100 / 12V 314 / 24V 100 / 24V 200.
  • Continuous current: 100A on the 12V 100Ah and 24V 100Ah; 200A on the 12V 314Ah and 24V 200Ah.
  • 24V halves the current at the same power; two 24V packs can be series-wired for 48V.
  • Weight and bay size often decide before the electrical math does.

1. The four models, side by side

ModelNominal energyUsable @80% DODMax cont. dischargeWeightBank limit
12V 100Ah1,280 Wh≈1.0 kWh100A10.5 kg4S4P
12V 314Ah4,019 Wh≈3.2 kWh200A26.5 kg4S4P
24V 100Ah2,560 Wh≈2.0 kWh100A20 kg2S4P
24V 200Ah5,120 Wh≈4.1 kWh200A40 kg2S2P

The 24V 200Ah has more energy than the 12V 314Ah but the same 100A discharge limit. At 25.6V that is about 2,560W continuous; the 12V 314Ah at 200A and 12.8V is also about 2,560W. The difference is the system voltage, not the peak power.

2. What capacity means in runtime

Runtime ≈ usable Wh ÷ average load. These are planning numbers, not guarantees: inverter losses, cold and ageing all reduce them.

Average load12V 100Ah12V 314Ah24V 100Ah24V 200Ah
50W (fridge + lights)≈20 h≈64 h≈41 h≈82 h
200W (van base load)≈5 h≈16 h≈10 h≈20 h
1,000W inverter≈1 h≈3.2 h≈2 h≈4.1 h
At 1,000W the 12V packs pull about 83A; at 2,000W about 167A. The 100Ah packs cannot sustain 2,000W, and the 314Ah can — but only if the cables, fuse and inverter are sized for it.

3. A simple decision rule

  • Weekend van, 12V fridge and lights, one-day autonomy: 12V 100Ah.
  • Full-time van, induction or coffee, 2–4 kWh/day: 12V 314Ah, or a 24V system if you are building from scratch.
  • Existing 24V boat or trolling motor: 24V 100Ah for a small motor/day boat; 24V 200Ah for longer sessions or a house bank.
  • Home backup, critical loads only: 24V 100Ah for 1 day; 24V 200Ah for 2 days; series-wire two for a 48V inverter (up to 2S4P / 2S2P).

If the math lands between two models, go up only if the extra weight and space are acceptable. A larger pack that does not fit the bay is worse than a smaller pack plus a second charge source.

4. Series and parallel limits

12V models support up to 4S4P: four in series, four in parallel. 24V models can also be series-wired in pairs for 48V: 100Ah up to 2S4P, 200Ah up to 2S2P.

Use the same model and similar age. Bring every battery to a similar state of charge before paralleling, and use equal cable lengths so the packs share current evenly.

Common questions

Can I mix a 100Ah and a 314Ah in one bank?
No. Different capacities share current unevenly; the smaller pack works harder and ages faster. Use the same model and similar age.
Is the 24V 200Ah better than the 12V 314Ah?
It depends on the system. The 24V pack has more energy and half the current at the same power, but it requires a 24V (or 48V with two in series) inverter. Choose the voltage your system already uses.

Models mentioned

12V 100Ah

1280 Wh

The everyday 12V pack. Light enough to swap by hand, with 100 A continuous output and room to expand to 20.48 kWh.

12V 314Ah

4019 Wh

Three times the capacity of the 100 Ah pack in one box — fewer parallel connections and a 200 A continuous / 600 A peak BMS.

24V 100Ah

2560 Wh

A native 25.6 V pack: half the current of a 12V pack at the same power. Series two for 48 V, parallel up to 2S4P.

24V 200Ah

5120 Wh

The largest capacity in the range: 5.1 kWh in one 24V case, 200 A continuous / 600 A peak, two in series for 48 V (2S2P).

Compare all models