Key takeaways
  • 12V models: maximum 4S4P (four series, four parallel, 16 batteries).
  • 24V models: two in series for 48V is allowed — 100Ah up to 2S4P, 200Ah up to 2S2P.
  • Series adds voltage, capacity stays the same; parallel adds capacity, voltage stays the same.
  • Use the same model, similar age and similar state of charge; equal cable lengths.

1. What series and parallel actually do

ConnectionVoltageCapacityExample
SeriesAdds upSame as one battery2 × 12V 100Ah → 25.6V 100Ah (2.56 kWh)
ParallelSame as one batteryAdds up2 × 24V 200Ah → 24V 400Ah (10.24 kWh)
Series + parallelSeries count × 12.8VParallel count × 100Ah12V 100Ah 4S4P → 51.2V 400Ah (20.5 kWh)

2. The limits for the four models

ModelSeriesParallelMaximum bank
12V 100Ah4S4P51.2V 400Ah (20.5 kWh)
12V 314Ah4S4P51.2V 1,256Ah (64.3 kWh)
24V 100Ah2S4P51.2V 400Ah (20.48 kWh)
24V 200Ah2S2P51.2V 400Ah (20.48 kWh)
The 24V manuals do list 48V configurations: two 24V 100Ah in series, up to four strings in parallel (2S4P, 20.48 kWh); two 24V 200Ah, up to two strings (2S2P, 20.48 kWh). Series only the same model and age, and never mix the two 24V models in one string.

3. Rules for a bank that stays balanced

  • Same model, same age, similar state of charge. Do not mix 100Ah and 314Ah in one bank.
  • Charge each battery fully before connecting, then let them rest and check the voltage.
  • Use equal cable lengths and the same lug/torque on every battery.
  • Fuse the bank positive close to the battery; size the cable for the inverter surge.
  • Do not rely on one BMS to protect the whole string — each battery protects itself.
  • Re-check torque and balance after the first week, then once a season.

4. Worked examples

24V from two 12V 314Ah: 2S → 25.6V 314Ah, 8,038 Wh. This is a common way to get 24V with the higher-capacity 12V pack; both batteries must be the same model and age.

48V from four 12V 100Ah: 4S → 51.2V 100Ah, 5,120 Wh. Four in series is the maximum for the 12V models; do not add a fifth.

48V from two 24V 200Ah: 2S2P with two more in parallel → 51.2V 400Ah, 20.48 kWh. This is the maximum for the 24V 200Ah; a third string is outside the limit.

5. Before you connect

Turn off all loads and chargers. Check polarity twice. Use insulated tools and remove metal jewellery. If you are not comfortable working with high-current DC, use a qualified installer — the bank can deliver enough current to weld a wrench.

Common questions

Can I connect two 12V batteries to make 24V?
Yes, 2S is within the 4S limit for the 12V models. Use the same model and age, charge both fully, and check the series voltage before connecting the load.
Can I connect two 24V batteries to make 48V?
Yes. Two 24V 100Ah in series make 25.6V + 25.6V = 48V (51.2V nominal, 100Ah per string). The manual lists 48V systems up to 2S4P. Use the same model and age, charge both fully first, and check the series voltage before connecting the load.

Models mentioned

12V 100Ah

1280 Wh

The everyday 12V pack. Light enough to swap by hand, with 100 A continuous output and room to expand to 20.48 kWh.

12V 314Ah

4019 Wh

Three times the capacity of the 100 Ah pack in one box — fewer parallel connections and a 200 A continuous / 600 A peak BMS.

24V 100Ah

2560 Wh

A native 25.6 V pack: half the current of a 12V pack at the same power. Series two for 48 V, parallel up to 2S4P.