Key takeaways
  • Charging is allowed from 0°C: 0–45°C on the 12V models, 0–50°C on the 24V models.
  • Discharge limits from the manuals: −20°C to 60°C (12V 100Ah), −20°C to 55°C (24V models), −10°C to 60°C (12V 314Ah).
  • The listed models do not have self-heating; warm the space or the pack before charging.
  • Store at 50–60% state of charge, 0–25°C, and top up every 3–6 months.

1. Charge and discharge are different limits

ActionLimitWhat happens
12V modelsCharge 0 – 45°CDischarge −20 – 60°C (100Ah), −10 – 60°C (314Ah)
24V modelsCharge 0 – 50°CDischarge −20 – 55°C
Storage0–25°C recommendedKeep 50–60% SOC; avoid months at 0% or 100%

2. Why charging below 0°C is blocked

Charging a lithium cell below freezing can plate lithium on the anode instead of intercalating it. That permanently reduces capacity and can create a safety risk. Both manuals start the charge window at 0°C for that reason; it is not a conservative setting to override.

3. No self-heating on these models

The listed 12V and 24V packs do not have internal heating. If you need to charge in freezing conditions, keep the battery in a heated compartment, insulate the bay, or warm the pack above 0°C before connecting the charger.

Do not use a heat gun or open flame on the case. Warm the space, not the plastic.

4. What “reduced capacity” means in practice

A cold pack still delivers energy, but the internal resistance rises and the BMS may cut off earlier under load. A 100Ah pack that gives 1.0 kWh at 20°C will give less at −10°C, and a large inverter may hit the low-voltage cutoff sooner.

Plan winter autonomy with a margin. If a system is already tight in summer, it will be short in winter — add capacity, reduce loads, or add a charge source.

5. Winter storage

  • Bring the pack to about 50–60% state of charge before storage.
  • Store in a dry place between 0 and 25°C, away from flood risk.
  • Disconnect loads that would drain it slowly (inverters, monitors).
  • Top up every 3–6 months; do not leave it at 0% for months.
  • Do not charge while frozen; warm it first.

Common questions

Can I discharge at −20°C?
The manuals rate discharge from −20°C (−10°C on the 12V 314Ah) to 55–60°C. Expect lower capacity and available current while cold; it recovers as the pack warms. Charging is the part that is blocked below 0°C.
What if I accidentally charged it below freezing?
Stop charging, disconnect the charger, and let the pack warm naturally. Do not keep charging to “test” it. If the BMS reports an error or the capacity drops noticeably, contact support with the event history from the app.

Models mentioned

12V 100Ah

1280 Wh

The everyday 12V pack. Light enough to swap by hand, with 100 A continuous output and room to expand to 20.48 kWh.

12V 314Ah

4019 Wh

Three times the capacity of the 100 Ah pack in one box — fewer parallel connections and a 200 A continuous / 600 A peak BMS.

24V 100Ah

2560 Wh

A native 25.6 V pack: half the current of a 12V pack at the same power. Series two for 48 V, parallel up to 2S4P.

24V 200Ah

5120 Wh

The largest capacity in the range: 5.1 kWh in one 24V case, 200 A continuous / 600 A peak, two in series for 48 V (2S2P).

Compare all models